Bosch Worcester condensing boiler fault codes
If your Bosch Worcester condensing boiler is showing a fault code it should be listed below, in some cases these can be fixed by the competent DIY'er-
PUMP HAS RUN DRY
Check system pressure, add water and then bleed if necessary.
HOT WATER NTC SENSOR DEFECTIVE
Check NTC sensor and connecting leads for circuit breaks and/or short circuits.
BREAK IN COMMUNICATION
Check connecting lead to programmer
KEYED PLUG NOT DETECTED
Insert keyed plug correctly, test and replace if necessary.
FAN SPEED TOO LOW
Check fan lead and connector, and fan; replace as necessary.
JUMPER 8-9 NOT CONNECTED
Connector not connected, link missing, or under floor heating limiter tripped.
CH FLOW NTC SENSOR DEFECTIVE.
Check CH flow NTC sensor and connecting lead.
SAFETY TEMPERATURE LIMITER IN CH FLOW HAS TRIPPED
Check system pressure, check safety temp. limiters, check pump operation, check fuse on pcb, bleed appliance.
FLAME NOT DETECTED
Is gas cock turned on? Check gas supply pressure, power supply, igniter electrode and lead, ionisation sensing electrode and lead, flue duct and CO2 level.
INTERNAL ERROR
Check electrical connector contacts, programmer interface module ignition leads and bus module are not loose; replace pcb or bus module if necessary.
FLAME DETECTED ALTHOUGH APPLIANCE IS SWITCHED OFF
Check electrode assembly, dry pcb. Flue clear?
FLAME DETECTED AFTER GAS SHUT OFF Check gas valve and wiring to gas valve. Clean condensation trap and check electrode assembly. Flue clear?
RESET BUTTON PRESSED BY MISTAKE
Press reset button again!
PLEASE WAIT INITIALISATION IN PROGRESS
24 Volt fuse blown, replace fuse!